How often should fire doors be inspected?

A fire door with a sign reading "Fire safety door, do not obstruct, do not keep open".
Photo by Sonny Sixteen on Pexels

Ask ten people how often fire doors should be inspected and you’ll get about six answers, most of them starting with “well, it depends”. For once, part of the answer is written into law. The rest is down to you.

This post covers England. The rules differ in Wales, Scotland and Northern Ireland.

The short answer

In a residential building with flats and a storey over 11 metres:

  • Communal fire doors: at least every three months.
  • Flat entrance doors: at least every 12 months, on a “best endeavours” basis.

For every other building, there’s no fixed frequency in law. The doors still have to work, and how often you check them should come out of the fire risk assessment.

Where the three months and 12 months come from

Regulation 10 of the Fire Safety (England) Regulations 2022 has applied since 23 January 2023. It covers multi-occupied residential buildings with storeys over 11 metres.

The responsible person has to:

  • Check the fire doors in the common parts every three months, including their self-closing devices. Lift landing doors aren’t included.
  • Use best endeavours to check every flat entrance door once a year, again including the closer.

The flat entrance doors are the awkward ones, because they sit behind someone’s front door, and not every resident is thrilled to see you.

What “best endeavours” means in practice

The law accepts that you can’t force your way into a flat to look at a hinge. It doesn’t accept “we sent one letter and gave up”.

The government’s fact sheet leaves it to the responsible person to decide how to engage with residents, for example by agreeing a date with them. If you still can’t get in, gather evidence of the steps you took, such as letters, emails and appointment attempts. That evidence is what shows you did what you could.

So a door you couldn’t get into isn’t a blank in the spreadsheet. Record it as a door you tried to inspect, with the reason you couldn’t, and keep trying.

Below 11 metres, and buildings that aren’t flats

Here the law doesn’t give you a number. The Fire Safety Order still requires fire precautions, fire doors included, to be maintained in efficient working order and good repair. The government’s fact sheet makes the same point for residential buildings under 11 metres: the doors still have to be able to provide adequate protection.

In practice, set the frequency in the fire risk assessment and base it on how the doors are used:

  • Heavy use means more checks. A door that’s slammed by delivery trolleys all day wears out faster than one at the end of a quiet corridor.
  • A history of problems means more checks. If doors keep getting wedged open or damaged, quarterly is a sensible starting point, whatever the height of the building.
  • Who uses the building matters. Sleeping risk, vulnerable occupants and people who don’t know the building all raise the stakes if a door fails.

Write the frequency down and say why. “Quarterly, because the communal doors take heavy footfall and have a history of being propped open” is far easier to defend than a frequency nobody can explain.

What a check actually involves

The regulations don’t ask for a specialist. The fact sheet says it shouldn’t normally be necessary to bring one in for these routine checks. You’d only call one in if a check turns up damage or problems that need a closer look.

The fact sheet describes the minimum as looking for obvious damage or problems, including:

  • alterations to the glazing or air grilles
  • gaps around the frame that look wrong
  • intumescent seals and hinges that are missing or poorly fitted
  • whether the self-closer pulls the door shut, and the door closes fully into the frame
  • visible damage to the door or the closer, deliberate or from wear and tear

That’s the routine check. A full fire door inspection, the kind you’d hand to a client as a report, goes further, door by door and component by component. Both have their place. The routine checks catch the wedged door and the broken closer between full inspections.

Don’t forget the residents

There’s one more duty that applies to every multi-occupied residential building with two or more flats and common parts, whatever its height. Residents must be told about fire doors when they move in, and every year after that:

  • keep fire doors shut when they’re not in use
  • don’t tamper with the self-closer or the door
  • report any damage or faults straight away

It’s the cheapest fire safety measure going, and it’s a legal requirement.

Keeping on top of it

The hard part isn’t knowing the frequency. It’s remembering, across dozens of buildings, which ones are due this month, which flats you still couldn’t get into, and whether the doors you flagged last time were actually fixed.

That’s the problem we built fire door inspections in Assura to solve. You set how often each client has their doors inspected, and for buildings over 11 metres Assura shows the legal minimum alongside it. Doors you couldn’t get into are recorded with the reason, not quietly skipped, and the Clients page shows when each building is next due.

However you track it, the rule of thumb is the same. Quarterly and annually where the law says so, a written and reasoned frequency everywhere else, and a record that shows you actually did it.


This article is general guidance, not legal advice, and does not guarantee compliance. Always refer to the current legislation and take advice from a competent professional for your specific building.